Ruckus ICX 7750 Switch Hardware Installation Guide
Part Number: 53-1003900-10
Installing the Ruckus ICX 7750
Installing the 1U, 1.5U, and 2U Universal Kit for Four-Post Racks (XBR-R000295)
FIGURE 13
Installing the Ruckus ICX 7750 in a 2-post rack
Proceed to
Installing the 1U, 1.5U, and 2U Universal Kit for Four-Post Racks
(XBR-R000295)
Use the following instructions to install a 1U, 1.5U, or 2U device in a 19-in. (48.3 cm) EIA rack using the 1U, 1.5U, and 2U Universal Kit
for Four-Post Racks (XBR-R000295).
The device can be installed so that the port side is either flush with the front posts or recessed with the non-port side flush with the rear
posts. A recessed position allows a more gradual bend in the fiber-optic cables connected to the device and less interference in the aisle
at the front of the rack.
NOTE
Hardware devices illustrated in these procedures are only for reference and may not depict the device you are installing into the
rack.
Installation requirements
Review the installation and facility requirements for your product before mounting the device. Refer to the hardware installation guide for
your product for more information.
Use Electronic Industries Association (EIA) standard racks. Provide space in a 19-in. (48.3 cm) EIA rack, as required for the device type,
with a minimum distance of 24 in. (609.60 mm) and a maximum distance of 32 in. (812.80 mm) between the front and back posts.
Time and items required
Allow 15 to 30 minutes to complete this procedure. Note the following requirements to ensure correct installation and operation.
The following items are required to install the device using the Universal Four-Post Rack Kit:
•
Clamps or other means of temporarily supporting the device in the rack