FIGURE 78 Connecting the Grounding Terminal With Optional (Two-Hole) Lug
1.
Grounding terminal
Two-lug information:
•
Manufacturer of grounding lug: Panduit
•
Part Number: LCD10-10AF-L
•
Screws: Two Machine Screws, M4-0.7x8
Connecting to the Grounding Terminal
Regardless of which lug you are using, perform the following steps to connect to the grounding terminal.
CAUTION
When installing a power supply unit, be sure to install the unit in the slot next to the location of the lug screw hole(s) because a blank
plate could interfere with the lug.
1.
Ensure that the rack in which the RUCKUS ICX 7550 is mounted is properly grounded and in compliance with local regulations.
2.
Ensure that there is a good electrical connection to the grounding point on the rack (no paint or isolating surface treatment).
3.
Crimp the included grounding lug to a grounding wire of at least 12 American Wire Gauge (AWG). The 12 AWG wire and grounding lug
should be crimped together using a proper tool.
4.
Attach the 12 AWG stranded copper wire to the grounding terminal on the RUCKUS ICX 7550 using the screw(s) included in the grounding
kit.
NOTE
You must connect the wire to the top hole of the grounding terminal, as shown in the previous figures.
5.
Attach the grounding wire to the grounding point on the rack.
NOTE
The terminal for the connection of a grounding conductor is not to be used with an aluminum conductor.
Power Supplies
Grounding the RUCKUS ICX 7550 Switch
RUCKUS ICX 7550 Switch Hardware Installation Guide
Part Number: 53-1005648-04
101
Содержание RUCKUS ICX 7550
Страница 10: ...RUCKUS ICX 7550 Switch Hardware Installation Guide 10 Part Number 53 1005648 04 ...
Страница 54: ...RUCKUS ICX 7550 Switch Hardware Installation Guide 54 Part Number 53 1005648 04 ...
Страница 66: ...RUCKUS ICX 7550 Switch Hardware Installation Guide 66 Part Number 53 1005648 04 ...
Страница 76: ...RUCKUS ICX 7550 Switch Hardware Installation Guide 76 Part Number 53 1005648 04 ...
Страница 90: ...RUCKUS ICX 7550 Switch Hardware Installation Guide 90 Part Number 53 1005648 04 ...
Страница 102: ...RUCKUS ICX 7550 Switch Hardware Installation Guide 102 Part Number 53 1005648 04 ...
Страница 108: ...RUCKUS ICX 7550 Switch Hardware Installation Guide 108 Part Number 53 1005648 04 ...
Страница 114: ...RUCKUS ICX 7550 Switch Hardware Installation Guide 114 Part Number 53 1005648 04 ...
Страница 141: ... 2021 CommScope Inc All rights reserved 350 West Java Dr Sunnyvale CA 94089 USA https www commscope com ...