ADCP-90-516 • Rev B • April 2019
Page 13
© 2019, CommScope, Inc.
Figure 10. ETSI Flush Mount Kit
3.3
Wall Mount Installation
Storage panel can be attached directly to a wall; however, CommScope recommends that it be
mounted on a 3/4-inch-thick plywood panel attached to the wall, in accordance with local fire
code. If the wall surface is uneven, shim the plywood as required to ensure a flat mounting
surface.
Also ensure that the fasteners used to attach the plywood panel are adequate to support the
weight of the plywood panel, the storage panel, and any other equipment attached to the
plywood. If attaching the storage panel directly to a wall, ensure that the selected fasteners can
support the weight of the storage panel. Install the storage panel as follows:
1. Remove the storage panel front cover by opening the cover approximately two inches (5
cm), then lifting the cover from the hinges (see
).
2. Position the storage panel in its designated location on the wall or plywood panel so FOT
patch cords enter the storage panel at the left (IFC or OSP cables can enter the module
from either the left or right side).
18990-A
M6
SCREW
STAR
WASHER
VCG
BASE
CAGE NUT
ETSI RACK
RIGHT-SIDE
BRACKET