507714-01
Page 17 of 52
Issue 1716
GDD95A / GDD92A Maximum Allowable Intake or Exhaust Vent Length in Feet
Table 7A.
Standard Termination at Elevation 0 - 10,000 ft
Number of 90°
Elbows Used
2" Pipe
2-1/2" Pipe
3" Pipe
Model
Model
Model
045
070
090
110
045
070
090
110
045
070
090
110
1
61
46
24
n/a
95
80
43
n/a
127
127
108
108
2
56
41
19
90
75
38
122
122
103
103
3
51
36
14
85
70
33
117
117
98
98
4
46
31
n/a
80
65
28
112
112
93
93
5
41
26
75
60
23
107
107
88
88
6
36
21
70
55
18
102
102
83
83
7
31
16
65
50
13
97
97
78
78
8
26
11
60
45
n/a
92
92
73
73
9
21
n/a
55
40
87
87
68
68
10
16
50
35
82
82
63
63
Concentric Termination Elevation 0 - 10,000 ft
Number of 90°
Elbows Used
2" Pipe
2-1/2" Pipe
3" Pipe
Model
Model
Model
045
070
090
110
045
070
090
110
045
070
090
110
1
53
38
22
n/a
90
70
39
n/a
111
111
104
104
2
48
33
17
85
65
34
106
106
99
99
3
43
28
12
80
60
29
101
101
94
94
4
38
23
n/a
75
55
24
96
96
89
89
5
33
18
70
50
19
91
91
84
84
6
28
13
65
45
14
86
86
79
79
7
23
n/a
60
40
n/a
81
81
74
74
8
18
55
35
76
76
69
69
9
13
50
30
71
71
64
64
10
n/a
45
25
66
66
59
59
*Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and
Exhaust must be same pipe size.
Содержание GDD92A
Страница 31: ...507714 01 Page 31 of 52 Issue 1716 Figure 52 Trap Drain Assembly Using 1 2 PVC or 3 4 PVC...
Страница 36: ...507714 01 Page 36 of 52 Issue 1716 045 3 110 5 090 4 070 3 Figure 59 Typical Wiring Diagram For GDD92A...
Страница 37: ...507714 01 Page 37 of 52 Issue 1716 045 3 110 5 090 5 070 3 Figure 60 Typical Wiring Diagram For GDD95A...
Страница 50: ...507714 01 Page 50 of 52 Issue 1716 Start Up Performance Checklist...