Service Manual -
DVC 09/12/18/24 SF Series
36
Index 1:
1:
Indoor or Outdoor DC Fan Motor(control chip is in fan motor)
Power on and when the unit is in standby, measure the voltage of pin1-pin3, pin4-pin3 in fan
motor connector. If the value of the voltage is not in the range showing in below table, the PCB
need
s
to be replaced.
DC motor voltage input and output(voltage: 220-240V~)
NO.
Color
Signal
Voltage
1
Red
Vs/Vm
280V~380V
2
---
---
---
3
Black
GND
0V
4
White
Vcc
14-17.5V
5
Yellow
Vsp
0~5.6V
6
Blue
FG
14-17.5V
DC motor voltage input and output(voltage :115V~)
NO.
Color
Signal
Voltage
1
Red
Vs/Vm
140V~190V
2
---
---
---
3
Black
GND
0V
4
White
Vcc
14-17.5V
5
Yellow
Vsp
0~5.6V
6
Blue
FG
14-17.5V
2. Outdoor DC Fan Motor (control chip is in outdoor PCB)
Power on ,and check if the fan can run normally, if the fan can run normally, the PCB must be
replaced
.
If the fan
does not
run normally, measure the resistance
between
each two pins. If the
resistance is not equal
between all pins
the fan motor must be replaced, otherwise the PCB must be
replaced.
3. Indoor AC Fan Motor
Power on and set the unit running in fan mode at high fan speed. After running for 15
seconds, measure the voltage of pin1 and pin2. If the value of the voltage is less than 100V
(208~240V power supply)or 50V(115V power supply), the PCB must be replaced.
41
Содержание A-DVC09SF-0
Страница 8: ...Service Manual DVC 09 12 18 24 SF Series 8 6 For B DVC09SF 0 For B DVC12SF 0 For B DVC18SF 1 ...
Страница 9: ...Service Manual DVC 09 12 18 24 SF Series 9 7 For B DVC24SF 1 ...
Страница 13: ...Service Manual DVC 09 12 18 24 SF Series 13 For A DVC24SF 1 ...
Страница 14: ...Service Manual DVC 09 12 18 24 SF Series 14 4 Refrigerant Cycle Diagram ...
Страница 42: ...Service Manual DVC 09 12 18 24 SF Series 42 47 P W N U ...
Страница 43: ...Service Manual DVC 09 12 18 24 SF Series 43 48 N V N W ...
Страница 55: ...Service Manual DVC 09 12 18 24 SF Series 55 This page intentionally left blank ...