background image

 

 

20 

5.4. 

 

Transferring the UPS to the Maintenance Bypass mode 

The following procedure is for a UPS equipped with an external Maintenance Bypass. 

Switching the UPS to the Maintenance Bypass mode means that the receivers are not 

protected against power failures. 

1.

 

Turn off the UPS inverter by pressing the OFF key for more than 0.5 seconds. The UPS will confirm 
shutdown with a single beep and switch to Bypass mode. 

2.

 

Switch the external Maintenance Bypass from UPS position to BYPASS position. 

3.

 

Disconnect the UPS from the power supply to completely shut down the UPS. Seconds later, the 
UPS turns off the LCD panel and stops the fans. 

4.

 

Turn the battery circuit breaker to the OFF position. 

5.5. 

 

Transferring the UPS from Maintenance Bypass mode to normal operation 

1.

 

Turn the battery disconnect switch located on the rear panel of the battery  module or near the 
battery cabinet for external batteries to the ON position. 

2.

 

Switch on the UPS power in the UPS switchboard. When power is applied, the LCD panel lights up 
and the fans start to run. A few seconds later, the UPS enters Bypass mode. 

Make sure the Bypass LED is on to go to the next step. 

3.

 

Switch the external Maintenance Bypass from BYPASS position to UPS position. 

4.

 

To turn on the power supply (start the inverter) press the ON button on the UPS display and hold 
it for more than 0.5 seconds. The UPS will confirm the start with an acoustic signal. 

5.

 

A few seconds later, the UPS turns on the inverter and starts normal operation. 

5.6. 

 

Battery test 

To activate the test function in the UPS, press the TEST button when the UPS is operating in normal, 
economic or converter mode. The UPS will run the test automatically and then go back to the previous 
working state. 
 
The  battery  test  can  be  performed  periodically  in  the  automatic  mode  after  the  appropriate 
configuration of the software connected to the UPS. 

5.7. 

 

Mute the audible alarm 

The UPS emits beeps while the UPS is operating on battery. To silence the UPS, press and hold the 
MUTE key for more than 0.5 seconds. 

5.8. 

 

Installing the software 

To take full advantage of the UPS, please install the provided ViewPower communication software. 
During the installation, follow the instructions on the computer screen. 
You must restart your computer after the installation process is complete. Restarting the computer 
will automatically launch ViewPower, as shown by the ViewPower icon in the Windows system tray. 

Środowisko pracy i eksploatacja UPS

 

Содержание COVER CORE 10K

Страница 1: ...E 6 10 kVA User manual The content of this document is the copyright of the publisher and may not be reproduced without prior permission The right to modify the design and specifications is reserved w...

Страница 2: ...2 LED indicators 10 4 3 LCD display 11 4 4 Alarm signals 12 4 5 LCD display letter abbreviations 12 4 6 UPS settings menu 13 4 7 Description of the UPS operation modes 15 4 8 UPS warnings and audible...

Страница 3: ...Compatibility EMC Test and Measurement Methods Radio Frequency Electromagnetic Field Immunity Test EN 61000 4 4 2004 A1 2010 Electromagnetic Compatibility EMC Test and Measurement Methods Test of immu...

Страница 4: ...ircuit should be protected with an appropriate overcurrent circuit breaker The UPS has its own battery power source so there may be voltage on the output strip even though the UPS is not connected to...

Страница 5: ...chanical damage shock and impact only transport the UPS in its original packaging All models of the CORE 6K and 10K power supplies are suitable for both horizontal and vertical mounting 2 1 Horizontal...

Страница 6: ...ower supply and enable its stable placement in a vertical position The set of stands includes short and long connecting elements depending on the width of the UPS set In order to place the power suppl...

Страница 7: ...y for the parallel operation version option 3 External battery connector 4 INTELLIGENT SLOT communication card slot LAN card AS400 RS485 5 RS 232 communication port 6 USB communication port 7 Remote E...

Страница 8: ...attery modules as in the figure below If it is necessary to extend the autonomy time the power supply has the option of connecting a battery with a much larger capacity thanks to the fact that it is e...

Страница 9: ...Cables should be connected and arranged in such a way that no one can accidentally disconnect them 3 4 Connection of remote EPO switch The UPS is equipped with an EPO port for connecting a remote eme...

Страница 10: ...n the events that occur on the UPS e g power failure low battery level The software also allows for ongoing monitoring and logging of UPS event history RS232 and USB ports cannot be used simultaneousl...

Страница 11: ...n to the previous menu page TEST UP Battery test Press and hold for more than 0 5 seconds during normal operation of the UPS to activate the test Up arrow Key to scroll up to the previous line in the...

Страница 12: ...r easy reading of the UPS status UPS The status of the LEDs determines the current operating status of the power supply and is described in the table below LED Mode Bypass Line Battery Fault UPS start...

Страница 13: ...tput voltage Hz output frequency Vdc battery voltage Load information Indicates the load level of 0 24 25 49 50 74 and 75 100 Indicates an overload condition Indicates a short circuit condition at the...

Страница 14: ...voltage Vac 230V mains voltage Vdc battery voltage Hz mains frequency 4 4 Alarm signals Battery mode Beep every 4 seconds Bypass mode Beep every 2 minutes Overload Beep 2x second Error Continuous tone...

Страница 15: ...240Vac output voltage 02 The output frequency 60 Hz CVCF mode 50 Hz Normal mode ATO Parameter 2 The output frequency Allows you to select the frequency 50Hz The output frequency is 50Hz 60Hz The outp...

Страница 16: ...ault 58Hz Parameter 3 Setting the upper frequency tolerance for ECO mode Possible settings 50Hz 52Hz 54Hz default 52Hz 60Hz 62Hz 64Hz default 62Hz 08 Bypass mode settings Parameter 2 OPN Bypass allowe...

Страница 17: ...le to make changes Parameter 2 Indicates the OP V output voltage Parameter 3 Indicates the UPS output voltage measured inside the UPS Using the arrow keys calibrate the value of the output voltage to...

Страница 18: ...the event of a power failure or when the supply voltage is beyond the tolerance allowing the output voltage to be kept within the required tolerance the UPS switches to battery operation The beep sou...

Страница 19: ...within 30 min Beeps every second 4 9 Warning codes Code Warning Code Ostrze enie 01 Batteries not connected 21 EC supply differences parallel operation 07 Battery overcharging 22 Differences on Bypas...

Страница 20: ...age is too low 14 Short circuit on the inverter output 1A Reverse power at the inverter output 21 Battery thyristor short circuit 24 Inverter relay shorted 2A Charger short circuit 31 CAN communicatio...

Страница 21: ...rmal operation Attention In order to obtain the maximum autonomy the batteries should be charged at least 10 hours after the first use The maximum capacity of the battery is obtained after two full di...

Страница 22: ...o go to the next step 3 Switch the external Maintenance Bypass from BYPASS position to UPS position 4 To turn on the power supply start the inverter press the ON button on the UPS display and hold it...

Страница 23: ...d damaging them Depending on the storage temperature the power supply should be connected at least every 6 months to charge the battery Typically the batteries are charged in 4 hours to 90 capacity bu...

Отзывы: