background image

 

 

18 

4.10. 

 

Fault Codes - Active in Fault Mode (Fault LED active)   

Code 

Icon 

Fail 

01 

BUS start error 

02 

High BUS voltage 

03 

BUS low voltage 

04 

BUS voltage unbalance 

11 

Inverter start error 

12 

Inverter voltage is too high 

13 

Inverter voltage is too low 

14 

 

Short circuit on the inverter output 

1A 

Reverse power at the inverter output 

21 

Battery thyristor short circuit 

24 

Inverter relay shorted 

2A 

Charger short circuit 

31 

CAN communication error 

41 

Overheated 

42 

CPU communication error 

43 

 

Overload 

60 

Inverter current too high 

6A 

Battery startup error 

6B 

PFC damage 

6C 

BUS voltage ripple 

6D 

Inverter current measurement error 

6E 

Damage to the SPS 12 V power supply 

Содержание COVER CORE 10K

Страница 1: ...E 6 10 kVA User manual The content of this document is the copyright of the publisher and may not be reproduced without prior permission The right to modify the design and specifications is reserved w...

Страница 2: ...2 LED indicators 10 4 3 LCD display 11 4 4 Alarm signals 12 4 5 LCD display letter abbreviations 12 4 6 UPS settings menu 13 4 7 Description of the UPS operation modes 15 4 8 UPS warnings and audible...

Страница 3: ...Compatibility EMC Test and Measurement Methods Radio Frequency Electromagnetic Field Immunity Test EN 61000 4 4 2004 A1 2010 Electromagnetic Compatibility EMC Test and Measurement Methods Test of immu...

Страница 4: ...ircuit should be protected with an appropriate overcurrent circuit breaker The UPS has its own battery power source so there may be voltage on the output strip even though the UPS is not connected to...

Страница 5: ...chanical damage shock and impact only transport the UPS in its original packaging All models of the CORE 6K and 10K power supplies are suitable for both horizontal and vertical mounting 2 1 Horizontal...

Страница 6: ...ower supply and enable its stable placement in a vertical position The set of stands includes short and long connecting elements depending on the width of the UPS set In order to place the power suppl...

Страница 7: ...y for the parallel operation version option 3 External battery connector 4 INTELLIGENT SLOT communication card slot LAN card AS400 RS485 5 RS 232 communication port 6 USB communication port 7 Remote E...

Страница 8: ...attery modules as in the figure below If it is necessary to extend the autonomy time the power supply has the option of connecting a battery with a much larger capacity thanks to the fact that it is e...

Страница 9: ...Cables should be connected and arranged in such a way that no one can accidentally disconnect them 3 4 Connection of remote EPO switch The UPS is equipped with an EPO port for connecting a remote eme...

Страница 10: ...n the events that occur on the UPS e g power failure low battery level The software also allows for ongoing monitoring and logging of UPS event history RS232 and USB ports cannot be used simultaneousl...

Страница 11: ...n to the previous menu page TEST UP Battery test Press and hold for more than 0 5 seconds during normal operation of the UPS to activate the test Up arrow Key to scroll up to the previous line in the...

Страница 12: ...r easy reading of the UPS status UPS The status of the LEDs determines the current operating status of the power supply and is described in the table below LED Mode Bypass Line Battery Fault UPS start...

Страница 13: ...tput voltage Hz output frequency Vdc battery voltage Load information Indicates the load level of 0 24 25 49 50 74 and 75 100 Indicates an overload condition Indicates a short circuit condition at the...

Страница 14: ...voltage Vac 230V mains voltage Vdc battery voltage Hz mains frequency 4 4 Alarm signals Battery mode Beep every 4 seconds Bypass mode Beep every 2 minutes Overload Beep 2x second Error Continuous tone...

Страница 15: ...240Vac output voltage 02 The output frequency 60 Hz CVCF mode 50 Hz Normal mode ATO Parameter 2 The output frequency Allows you to select the frequency 50Hz The output frequency is 50Hz 60Hz The outp...

Страница 16: ...ault 58Hz Parameter 3 Setting the upper frequency tolerance for ECO mode Possible settings 50Hz 52Hz 54Hz default 52Hz 60Hz 62Hz 64Hz default 62Hz 08 Bypass mode settings Parameter 2 OPN Bypass allowe...

Страница 17: ...le to make changes Parameter 2 Indicates the OP V output voltage Parameter 3 Indicates the UPS output voltage measured inside the UPS Using the arrow keys calibrate the value of the output voltage to...

Страница 18: ...the event of a power failure or when the supply voltage is beyond the tolerance allowing the output voltage to be kept within the required tolerance the UPS switches to battery operation The beep sou...

Страница 19: ...within 30 min Beeps every second 4 9 Warning codes Code Warning Code Ostrze enie 01 Batteries not connected 21 EC supply differences parallel operation 07 Battery overcharging 22 Differences on Bypas...

Страница 20: ...age is too low 14 Short circuit on the inverter output 1A Reverse power at the inverter output 21 Battery thyristor short circuit 24 Inverter relay shorted 2A Charger short circuit 31 CAN communicatio...

Страница 21: ...rmal operation Attention In order to obtain the maximum autonomy the batteries should be charged at least 10 hours after the first use The maximum capacity of the battery is obtained after two full di...

Страница 22: ...o go to the next step 3 Switch the external Maintenance Bypass from BYPASS position to UPS position 4 To turn on the power supply start the inverter press the ON button on the UPS display and hold it...

Страница 23: ...d damaging them Depending on the storage temperature the power supply should be connected at least every 6 months to charge the battery Typically the batteries are charged in 4 hours to 90 capacity bu...

Отзывы: