Modbus TCP
Device supports Modbus protocol for communication with SCADA systems. Device use
Modbus TCP protocol.
TCP port
is set to
502
by default. Port can be changed using TSensor
software or web interface. Only two Modbus clients can be connected to device at one
moment. Modbus device address (Unit Identifier) can be arbitrary. Modbus write command
is not supported. Specification and description of the Modbus protocol is free to download
on: www.modbus.org.
Supported Modbus commands (functions):
Command
Code
Description
Read Holding Register (s)
0x03
Read 16b register(s)
Modbus device registers. Address could be by 1 higher, depending on type used
communication library:
Address [DEC] Address [HEX] Value
Type
49
0x0031
Measured temperature
Int*10
50
0x0032
Measured relative humidity
Int*10
51
0x0033
Measured computed quantity
Int*10
52
0x0034
Measured atmospheric pressure, CO
2
concentration
Int*X
53
0x0035
Dew point temperature
Int*10
54
0x0036
Absolute humidity
Int*10
55
0x0037
Specific humidity
Int*10
56
0x0038
Mixing ration
Int*10
57
0x0039
Specific enthalpy
Int*10
4149
0x1035
Serial number high
BCD
4150
0x1036
Serial number low
BCD
4151
0x1037
Device type
HEX
20481
0x5001
Temperature low limit
Int*10
20482
0x5002
Temperature high limit
Int*10
20483
0x5003
Relative humidity low limit
Int*10
20484
0x5004
Relative humidity high limit
Int*10
20485
0x5005
Computed quantity low limit
Int*10
20486
0x5006
Computed quantity high limit
Int*10
20487
0x5007
Temperature hysteresis
Int*10
20488
0x5008
Temperature time-delay
DEC
20489
0x5009
Relative humidity hysteresis
Int*10
20490
0x500A
Relative humidity time-delay
DEC
20491
0x500B
Computed quantity hysteresis
Int*10
20492
0x500C
Computed quantity time-delay
DEC
20493
0x500D
Temperature alarm state
String
20494
0x500E
Relative humidity alarm state
String
20495
0x500F
Computed quantity alarm state
String
20496
0x5010
Atmospheric pressure, CO
2
concentration low limit
Int*X
20497
0x5011
Atmospheric pressure, CO
2
concentration high limit
Int*X
20498
0x5012
Atmospheric pressure, CO
2
concentration hysteresis
Int*X
20499
0x5013
Atmospheric pressure, CO
2
concentration alarm state
String
20500
0x5014
Atmospheric pressure, CO
2
concentration time-delay
DEC
20501
0x5015
Min. temperature memory
Int*10
20502
0x5016
Max. temperature memory
Int*10
20503
0x5017
Min. relative humidity memory
Int*10