Initial power-up

1. Update the Atena Easy firmware to 3.8.3 or higher;
2. Switch off the power supply of the Atena Easy Panel;
3. Connect the LAN Module to the panel: use the serial flat interface cable to connect to ATENA EASY 
Panel;
4. Turn on the power supply;
5. Load the LAN module in the System tree of Atena Prog. Connect to the Module with micro USB 
and read the parameters (PC ID “1234” from default);
6. After reading, in General Settings put for Control Panel Type – “Fire Panel” and Enable the Modbus 
Server;
7. In Network Settings set Manual settings, then type the desired IP address, NetMask and Gateway;
8. Write the parameters to the panel (PC ID “1234”, User Code “0000”);
9. Connect the Ethernet cable to the LAN module connector;
10. Set manually the IP parameters on Atena Easy panel;
11. Wait until the 41ECN000 module enters into normal operation mode - the Status LED
is blinking green and the Net State LED lights on in green. The time for initial power-up is
up to 90 sec.;
12. After, connecting with Atena Manager, set manually IP parameters and uploading the TDF file 
programming of the panel.

41ECN000 - Installation Instruction

 

General Information

41ECN000 is LAN communication module, designed for operation via serial communication with ATENA EASY fire alarm panel. The module 
transmits the incoming events to ATENA MANAGER monitoring software through LAN network. The general application of the module

 is

 

to send 

messages 

for events 

to monitoring center or end-user. The module 

is mounted into the ATENA EASY metal box

.

 The programming of 41ECN000 

is via ATENA PROG programming software.

Elements Description 

B

 - Mounting holes.

C

 - Terminal row:

       

± V 

- Power supply 9-30VDC - not used!

       Attention: The power supply is from the panel via the serial interface cable!     
       

I/O1-6 

- Programmable input/output

 

(via ATENA PROG)

;

       

Com 

- Common Ground;

       

AC 

- Not used.

E

 

Jumper to restore of the factory settings*.

F

 -

 

LED Indication*

*

:

       

Status 

- LED for status of the connection with ATENA EASY panel

;

       

Tx 

- LED for indication of transmitting events to ATENA MANAGER

;

       

Net State 

- LED for the state of the connection with ATENA EASY panel.

G

 - LAN network connector

:

Ѓ

 - LED LAN Action (green);

 - LED LAN Link (yellow). 

H

 -

 

Serial interface for connection to ATENA EASY.

1

Put 

 

 

jumper 

 

to

 

 reset 

 

the

 

 module

 

 parameters 

 

by

 

 default.

*

The detailed description of the LED indication is shown on page 2.

18020976, Rev

A, 10/2018

Internal structure of a 
programmable output

R

L

 = 

1

20

W

10K

1K

I/O 1-6

41ECN000

ё

 30

V

+V

Status

Micro USB

V

-   V+

I/O1

Jumper

Tx

Net
State

I/O2

I/O3

I/O4

I/O5

I/O6

Com

AC

Comelit Group S.p.A. 

 Via Don Arrigoni 5 - 24020 Rovetta 

S. Lorenzo BG Italy 

tel. +39 0346 750 011 

fax +39 0346 71436  

[email protected]

Technical Specifications

• 

Main power supply:

 9-30VDC;

• 

Reversed polarity protection

;

• 

Current consumption:

  - Normal operation mode (standby): 80mA
  - Maximal consumption: 150mA
• 

6 Programmable In/Out: 

OC type 

• 

Micro USB input

 for programming

• 

Operating temperature:

 0°C ÷ +60°C

 Restoring

 

of the factory defaults

• 

Dimensions:

 50x90mm

• Parameters of the inputs:

 - Permissible input voltage:  0 

-

 20V

 - Signal filtering period: 300ms
 - Threshold of operation: 1.3V
 - Hysteresis: ±0.4V

ATTENTION: Carefully read through this manual prior to installing 
the device!  