Mains pro 1.6.1 Global Guide
52
12.1.1 Group: Basic
Uin
Selection of the measurement range to adjust the HW for maximum accuracy.
230 V
the unit measures 230 VAC phase-ground with max over-range 130% (300 VAC)
400 V
the unit measures 400 V phase-phase with max over-range 130% (520 VAC)
120 V
the unit measures 120 VAC phase-ground or on the secondary winding of the VT with
max over-range 130% (156 VAC)
Default setting
230 V
System
Selection of single phase or three-phase application. In case of single phase setting, the voltage on last two
phases and voltage asymmetry are not measured.
3ph
the unit measures 3-phase system
1ph
the unit measures single-phase system
Default setting
3ph
DispT [min]
Setting of display backlight timeout since the last button activity.
Range
1..60 min
0 min
= OFF, display is set to permanent backlight
Default setting
0 min
Auto FR
Enables or disables the functionality of the automatic fault reset by internal timer.
ENABLED
the functionality is enabled
DISABLED
the functionality is disabled
Default setting
ENABLED