InteliVision 18Touch 1.0 Global Guide
24
6.2 IV18T connection to a Multiple gen-set
6.2.1 USB / RS-232 connection via I-LB+.
Image 6.5 Connection to the controllers via I-LB+
Note:
The I-LB+ module enables monitoring and configuration of up to 32 controllers connected via a CAN(2)
intercontroller bus. It is also possible to use I-LB+ for single controller connection. It is recommended to use a
USB connection because of the communication bandwidth it provides (rate). It is also possible to use the RS-
485 interface on the controllers’ side instead of CAN2.
I-LB+ hardware setup
All jumpers in these positions
HW/SW control
Does not matter
ComAp/ModBus
Open
ADDR1/ADDR2
Selection of CAN address. Open = ADDR1, Close = ADDR2 It is possible to use up
to two I-LB+ devices in direct mode on the CAN(2) bus. Leave the jumper open when
using one I-LB+ module. The other I-LB+ module has to have this jumper closed. (See
I-LB+ module for further details.)
DIRECT/MODEM
Open
RS485/RS232
Selection of com port (jumper is in RS232 position) / Does not matter
Comm. speed.
Does not matter
RS485 120 Ohm
Open = terminator not connected, Closed = terminator connected
CAN 120 Ohm
Open = terminator not connected, Closed = terminator connected
RS-232 / USB
Open (USB Disable) / Closed (USB enabled)
Table 6.4 I-LB+ settings