InteliPro, SW version 1.4,
©
ComAp
–
April 2014
InteliPro 1.4 Comprehensive Guide - rev. 1
4-37
Default setting: 256
Nominal RPM
[-]
Number of the machine nominal revolutions per minute
Step:
1 [-]
Range:
100 - 4000
Default setting:
1500
Pole Slip Lim
[°]
The load angle limit setting
Step:
1°
Range:
90 - 180
Default setting:
100
PS Trp BO
[ Trp 1 / Trp 2 / Trp 1+2 / None ]
Selection of trip binary output for pole slip protection.
Default setting: None
MaxParallTime
MaxParallTime [s]
Timer of the maximum parallel time protection.
Step:
0,1 s
Range:
0,1
–
1800,0 s
Default setting: 300,0 s
MaxPT Trp BO
[Trp 1 / Trp 2 / Trp 1+2 / None]
Selection of trip binary output for maximum parallel time protection.
Default setting: None
CU Analog In
Setpoints in this group are used for protection on DC analog inputs of the unit.
CU AI1 Wrn, CU AI2 Wrn, CU AI3 Wrn
Level of warning type of protection assigned to analog input 1, 2 or 3 of the unit respectively. The step,
decimals, range and units are given by configuration of the appropriate output.
CU AI1 Trp, CU AI2 Trp, CU AI3 Trp
Level of trip assigned to analog input 1, 2 or 3 of the unit respectively. The step, decimals, range and
units are given by configuration of the appropriate output.
CU AI1 Del, CU AI2 Del, CU AI3 Del
[s]
Delay of protections assigned to analog input 1, 2 or 3 of the unit respectively. It is the same for
warning alarm and trip.
Step:
1 s
Range:
0 - 600 s
Default setting: 5 s