InteliPro, SW version 1.4,
©
ComAp
–
April 2014
InteliPro 1.4 Comprehensive Guide - rev. 1
4-26
Default setting: 10 %In
Q Min
[%S]
Threshold for the reactive power measurement
Step:
1 %S
Range:
1
–
10 %S
Default:
5 %S
QU Del 1 [s]
Time delay for opening the GCB (CB1)
Step:
0,01 s
Range:
0,00
–
1,00 s
Default:
0,50 s
QU Del 2 [s]
Time delay for opening the MCB (CB2)
Step:
0,01 s
Range:
1,00
–
2,00 s
Default:
1,50 s
QU Trp Gen
[Trp 1 / Trp 2 / Trp 1+2 / None]
Selection of trip binary output for QU protection
Default: None
QU Trp Mns [Trp 1 / Trp 2 / Trp 1+2 / None]
Selection of trip binary output for QU protection
Default: None
f<>
f>, f>>, f<, f<<
[Hz]
Threshold of 1st and 2nd stage overfrequency and 1st and 2nd stage underfrequency protection
respectively.
Step:
0,01 Hz
Range:
0,00 - 70,00 Hz
0 = OFF, the appropriate stage of frequency protection is disabled
Default setting:
f>
51,5 Hz
f>>
52 Hz
f<
47,5 Hz
f<<
47 Hz
f> del, f>> del, f< del, f<< del [s]
Delay of the appropriate stage of the frequency protection.
Step:
0,01 s
Range:
0,00 - 600,00 s
Default setting:
f> Del
90,00 s
f>> Del
0,50 s
f< Del
20,00 s