B07 Zero Power Mode Delay
Units:
minutes [min]
Step:
1 minute
Range:
0-360 minutes
Default value:
0
The controller is switched to Zero Power Mode when there is no user interaction with the controller for
the preset time. Zero Power Mode is disabled in AMF mode. Value 0 also disables this function. For
the controller wake up press button
Start
. The controller will not switch to Zero
Power Mode if any alarm is active.
B08 Light Tower Mode
Units:
Step:
Range:
1,2
Default value:
1
This setpoint is available only when
is disabled. When this setpoint is enabled,
the controller is switched to special operation mode. First screen was changed and generator voltage
measurement is hides in this operation mode.
Setpoint code
Value
Meaning
E08
1
Disable
E08
2
Enable
First main screen shows battery voltage, running hours and engine status (stop,
starting/stopping, run) via symbol in light tower reflector (upper left corner).
Second screen shows all analog values which are available. (Oil Pressure, Coolant
Temperature; Fuel Level and Battery Voltage)
Last screen is event log.
Figure 10.4
L
IGHT
T
OWER SCREENS
Содержание InteliNano NT Plus
Страница 36: ...InteliNano NT Plus SW version 2 0 1 x ComAp July 2015 36 Figure 8 1 BINARY OUTPUT SETTING EXAMPLE ...
Страница 45: ...InteliNano NT Plus SW version 2 0 1 x ComAp July 2015 45 Figure 9 1 BINARY INPUT SETTING EXAMPLE ...
Страница 46: ...InteliNano NT Plus SW version 2 0 1 x ComAp July 2015 46 3x 3x Figure 9 2 ANALOG INPUT SETTING EXAMPLE ...
Страница 77: ...InteliNano NT Plus SW version 2 0 1 x ComAp July 2015 77 Figure 12 2 ...