InteliNano-NT Plus, SW version 2.0.1.x,
©ComAp – July 2015
43
O11 Glow Plugs
This output is activated before each cranking procedure for Prestart Time but maximally for 8s!
Prestart Time
≤ 8 s
Maximum
Cranking Time
0 - 60 s
Maximum
Cranking Time
0 - 60 s
Cranging Fail
Pause 8 s
Cranging Fail
Pause 8 s
Gen-set start failed
On
Off
Starter Output
Time
Start
Glow Plugs
Output On
Prestart Time
> 8 s
Maximum
Cranking Time
0 - 60 s
Maximum
Cranking Time
0 - 60 s
Cranging Fail
Pause 8 s
Cranging Fail
Pause 8 s
Gen-set start
failed
On
Off
Time
Start
Glow Plugs
Output On
8 s
Starter Output
Prestart Time
> 8 s
Maximum
Cranking Time
0 - 60 s
Gen-set start failed – shutdown,
if the voltage or frequency are not in
the limit
On
Off
Time
Start
Engine run
Max. Stab. Time 7 s
Min. Stab. Time
Starter Output
8 s
Glow Plugs
Output On