![ComAp InteliNano NT Plus Скачать руководство пользователя страница 25](http://html.mh-extra.com/html/comap/intelinano-nt-plus/intelinano-nt-plus_reference-manual_2638959025.webp)
InteliNano-NT Plus, SW version 2.0.1.x,
©ComAp – July 2015
25
Analog inputs
4.10
The analog inputs are designed for resistive automotive type sensors like VDO or DATCON. The
sensors are connected either by one wire (the second pole is sensor body) or by two wires.
C
AUTION
!
In case of grounded sensors connect the terminal
to the engine body as near the sensor as
possible!
C
AUTION
!
In case of isolated sensors connect the terminal
to the negative power supply terminal of the
controller as well as the opposite poles of the sensors!
N
OTE
:
Value #### is displayed when measured value is out of range or sensor’s wire is broken.
+ -
O
il
P
re
s
s
u
re
(
T
1
5
)
A
n
a
lo
g
C
O
M
(
T
1
0
)
Figure 4.20
WIRING OF ANALOG INPUTS
-
GROUNDED SENSORS