The output can be used for indication of the MCB position.
14.2.1.74
Binary output: LdShed stage 1
Related FW
standard v3.1.0
Description
This output is used for control of first load group. This is the group which is
disconnected as
first
one when the load shedding function becomes active.
Connect
least important
loads to this group.
N
OTE
:
Learn more about load shedding in the separate chapter
Load shedding
.
14.2.1.75
Binary output: LdShed stage 2
Related FW
standard v3.1.0
Description
This output is used for control of second load group. This group is
disconnected as
second
one when the first group is already disconnected
and the condition for disconnecting of next group is still fulfiled.
N
OTE
:
Learn more about load shedding in the separate chapter
Load shedding
.
14.2.1.76
Binary output: LdShed stage 3
Related FW
standard v3.1.0
Description
This output is used for control of third load group. This group is disconnected
as
last
one when the first two groups are already disconnected and the
condition for disconnecting of next group is still fulfiled.
N
OTE
:
Learn more about load shedding in the separate chapter
Load shedding
.
14.2.1.77
Binary output: CtrlHeartBeat
Related FW
standard v3.1.0
Description
The output provides alternating signal with rate 500ms active / 500ms
inactive while the controller is
operational
, i.e. it has passed all checks after
startup and no failure was detected.
If the output does not provide the alternating signal it may indicate following:
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...