![ComAp InteliMains NT IM-NT Скачать руководство пользователя страница 254](http://html1.mh-extra.com/html/comap/intelimains-nt-im-nt/intelimains-nt-im-nt_reference-manual_2638901254.webp)
InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
254
OFF.
N
OTE
:
See the chapter
Regulation loops overview
for general information about
regulation loops and their adjustment.
11.2.10.10
Setpoint: Load int
Group
Sync/Load Ctrl
Range [units]
0 .. 100 [%]
Related FW
standard v3.1.0
Description
This setpoint adjusts the relative integration factor (I-factor) of the load
control PI loop. The gain factor (P-factor) for the load control loop is adjusted
by the setpoint
A
PPLICATION
L
OAD GAIN AND
L
OAD INT SETPOINTS ARE ACTIVE DURING
:
MCB,
MGCB
parallel to mains operation in any mode where IM-NT
load control loop is active (see setpoint MLoad ctrl PtM),
including load ramps
BTB
BusLeft or BusRight BaseLoad control in any mode
where IM-NT load control loop is active (see setpoint
MultiLoad ctrl), including load ramps
N
OTE
:
See the chapter
Regulation loops overview
for general information about
regulation loops and their adjustment.
11.2.10.11
Setpoint: MGCB open lev
Group
Sync/Load Cont
Range [units]
0 .. 100 [%]
Related FW
standard v3.1.0
Description
This setpoint adjusts the end point of the bus unloading ramp, i.e. power level
at which the MGCB is opened. If this level is not reached within time period
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...