InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
224
11.2.8 Group: AMF settings
11.2.8.1
Setpoint: EmergStart del
Group
AMF settings
Range [units]
0 .. 600 [s]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint sets the delay between the mains failure and the command to
start the gen-set group, i.e. closing the binary output Sys start/stop.
N
OTE
:
Link the output Sys start/stop with the inputs Sys start/stop at the gen-set
controllers to achieve the automatic start. Gen-set controllers have to be in
AUT mode in order to react to this input.
11.2.8.2
Setpoint: FwRet break
Group
AMF settings
Range [units]
0 .. 60.0 [s]
Related FW
standard v3.1.0
Force value
possible
YES
Description
MGCB
APPLICATION
This setpoint sets
- the delay between MGCB opening and MCB
closing during the return to mains when reverse
synchronizing (or mains parallel run) is not
enabled.
and
- the delay between MCB opening and MGCB
closing in TEST Mode, when ReturnTo mains =
ENABLED and power cut comes.
MCB
APPLICATION
This setpoint sets the delay between last GCB
opening (from CAN2 bus) and MCB closing during
the return to mains when reverse synchronizing
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...