InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
189
OFF
The backlight is off all the time
NO
TIMEOUT
The backlight is on all the time
11.2.2.21
Setpoint: UserBtn pulse
Group
Basic settings
Range [units]
0.2 .. 10.0 [s]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint adjusts the duration of User Button 1..16 pulse. For more
information read the description of LBO
11.2.2.22
Setpoint: ImpCountDef1-4
Group
Basic settings
Range [units]
0 .. 65535 [-]
Related FW
standard v3.2.0
Force value
possible
YES
Description
This setpoint adjusts the value to which the corresponding Impulse counter
statistic is set when the binary input
ImpCountSet1-4
.
11.2.2.23
Setpoint: ConvCoefPulse1
Group
Basic settings
Range [units]
1 .. 65000 [/X]
Related FW
standard v3.1.0
Description
The conversion ratio between incoming pulses at binary inputs PulseCounter
1/2/3/4 and output statistic values PulseCounter 1/2/3/4. The ratio defines
how many pulses (rising edges) have to be sensed at the input in order to
increase the output value. Unfinished “invisible” parts are stored in the
controller even in the case of power supply failure. Physical unit of the output
statistic value has to correspond to the ratio unit “/X”.
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...