7.26 Languages and Translator tool in GenConfig
For detailed description of Languages and Translator tool please refer to GenConfig interactive help
(press F1 when in corresponding tab or open Help -> GenConfig Help).
7.27 Power Formats
InteliMains allows user to choose from several Power Formats that affect dimensions in which values
and some setpoints are interpreted or adjusted. Power formats may be changed in Miscellaneous tab
in GenConfig. There are following Power Formats available:
1 kW kVAr kVA kX V
0,1 kW kVAr kVA kX V
0,01 MW MVAr MVA MX kV
0,01 MW MVAr MVA MX V
It is necessary to use power formats in MX when the sum of nominal power of gen-sets or any power
in the system (e.g. power imported from Mains) is expected to be above 32000 kW.
N
OTE
:
Range of some setpoints and values is changed significantly when different Power Formats are
selected.
Last Power Format is designed to be used in combined Power/High Voltage and Low Voltage
instalations. High voltage is then interpreted in Volts (e.g. 33256V instead of 33kV).
Last two Power Formats can be used in combination on one CAN bus.
7.28 System Start/Stop
Many functions in InteliMains are directly connected to the standard functions of InteliGen and
InteliSys that form complete system together with InteliMains. For proper function of the system,
System start and stop signal needs to be used properly. Below there is scheme that shows how to use
the Binary Output S
YS
S
TART
/S
TOP
in the system using just CAN wiring (no physical wiring is needed
to share the starting and stoping signal into all controllers in the system).
InteliGen/
InteliSys
InteliGen/
InteliSys
InteliGen/
InteliSys
InteliGen/
InteliSys
BTB feedback
CAN
SHBOU
T2
SHBOU
T1
SHBIN
1
SHBIN
2
SHBIN
1
SHBIN
2
SHBIN
1
SHBIN
2
SHBIN
1
SHBIN
2
SHBOUT1-1
Sys Start/Stop
SHBOUT1-2
BTB feedback
InteliMains1
InteliMains2
SHBOUT2-1
Sys Start/Stop
Sys S/S from IM2
BTB feedback
Sys S/S from IM1
M2 Start
(sheet output)
Sys S/S from IM1
BTB feedback
Sys S/S from IM2
M1 Start
(sheet output)
Shared binary inputs
Logical Group 2
Logical Group 1
Figure:
Preparation of correct system start/stop function for two logical groups
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...