InteliMains 210 Global Guide
433
Related FW
2.0.0
Related applications
MCB, MGCB
Comm object
38
Description
Use this input to start and stop the gen-set in AUTO mode and TEST mode.
Taken action in MCB, MGCB application (AUTO Mode)
Active
System Start/Stop is activated regardless the Mains is OK
MGCB is closed in case of MGCB application
Parallel operation - Baseload, import/export
Reverse synchronising in case of mains return
Inactive
System Start/Stop deactivated
MGCB opened
Note:
In the SPTM and AMF application there are more LBIs that can influence the state of the
application and can be in the collision with the Common LBI Remote Start/Stop.
Note:
This function is not supported in BTB application.
Remote Start/Stop
back to Logical binary inputs alphabetically
LBI: T
Related FW
2.0.0
Related applications
MCB, MGCB, BTB
Comm object
125
Description
Binary input activates time stamp writing to history depending on Date/Time:Time stamp act and Time
Stamp Per setpoints.
Time Stamp Act