InteliMains 210 Global Guide
171
Setpoint group
Process Control
Related FW
2.0.0
Range [units]
0 .. 32 000 [kW]
Default value
1 000 kW
Alternative config
NO
Step
1 kW
Comm object
8775
Related applications
MCB, MGCB, BTB
Description
Required total load of the gen-set group in parallel to mains operation in baseload mode (setpoint
= Baseload).
#System BaseLoad
Setpoint group
Process Control
Related FW
2.0.0
Range [units]
0,60 .. 1,20 [-]
Default value
1,00 [-]
Alternative config
NO
Step
0,01 [-]
Comm object
8776
Related applications
MCB, MGCB, BTB
Description
Required gen-set power factor when the group of gen-sets is running parallel to the mains. The PF is
regulated locally in each controller by PF control regulation loop, VARsharing is not active.
#System Power Factor
Subgroup: Mains coupling
Setpoint group
Process
Control
Related FW
2.0.0
Range [units]
Enabled / Disabled [-]
Default value
Disabled
Alternative config
NO
Step
[-]
Comm object
11037
Related applications
MCB, MGCB, BTB
Description
Setpoint adjusts behavior of BTB in systems where mains is present on both sides of bus.
Enable - BTB can be closed when there is mains on both sides
Disable - BTB cant be closed, when there is mains on both sides
Note:
Passive phase/voltage check is performed before mains coupling.
Mains Coupling