IG-IOM and IGS-PTM modules are I/O extension modules equipped with 8 binary inputs, 8 binary
outputs, 4 analogue inputs and one analogue output. The module can be used for AMF25, MRS15,
16, 19 only.
Binary inputs and outputs are configurable the same way like inputs and outputs on iL.
Analogue inputs are configurable like iL with the limitation that the binary and tristate mode
cannot be used on PTM module.
The protection of analogue IOM/PTM inputs is activated by overcrossing the limits, active only
when the engine is running.
IG-IOM analogue inputs are resistive (the same parameters like IL-NT) 0
-2,4 k
. The
module IOM is designed for especially VDO resistive sensors.
IGS-PTM analogue inputs are configurable by jumpers to ranges 0-250
, 0-100mV, 0-20mA.
The module can be used especially for Pt100 sensors and current sensors. The module PTM
is not suitable for VDO temperature sensor.
Hint:
- For connection details please refer to chapter
Extension modules (CAN bus) connection
- For a description of setting IGS-PTM module with current/voltage sensors please see the Extension
modules manual.
- When module is not configured by LiteEdit SW, controller does not show related values and
setpoints
- If IGS-PTM is not communicating to a controller, ShutDown protection on controller is activated.