InteliLite Global Guide
188
Setpoint group
Engine settings
Related FW
1.2.1
Range [units]
Disabled / 1 .. 60 [s]
Default value
30 s
Alternative config
YES
Step
1 s
Comm object
10685
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Visible only if the logical binary output
is configured
Description
If the controller does not see the fuel increase during fuel transfer within this time alarm
will be displayed and the
will be turned off. Alarm
will be displayed but this alarm becomes immediately inactive and it will be
possible to delete this message by the Fault reset button. If the fault is deleted the controller will initiate the
transfer again.
Transfer Wrn Delay
Subgroup: Maintenance
Setpoint group
Engine settings
Related FW
1.2.1
Range [units]
0 ... 9 999 [h] / Disabled
Default value
1 000 h
Alternative config
NO
Step
1 h
Comm object
10528
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Maintenance timer 1 counts down when engine is running. If reaches zero, an alarm appears. When the
value 10000 is set, than the Maintenance function is disabled and counter does not count. Counter value
disappear from controllers statistics.
Maintenance Timer 1
Содержание InteliLite MRS16
Страница 40: ...InteliLite Global Guide 40 4 4 12 Example of MRS Wiring ...
Страница 55: ...InteliLite Global Guide 55 ...
Страница 56: ...InteliLite Global Guide 56 ...
Страница 57: ...InteliLite Global Guide 57 ...
Страница 58: ...InteliLite Global Guide 58 ...
Страница 59: ...InteliLite Global Guide 59 ...
Страница 60: ...InteliLite Global Guide 60 Setpoint Screens ...
Страница 61: ...InteliLite Global Guide 61 History Log ...
Страница 62: ...InteliLite Global Guide 62 ...
Страница 63: ...InteliLite Global Guide 63 ...
Страница 64: ...InteliLite Global Guide 64 ...
Страница 65: ...InteliLite Global Guide 65 5 3 3 Browsing alarms ...
Страница 66: ...InteliLite Global Guide 66 5 3 4 Password Enter password ...
Страница 67: ...InteliLite Global Guide 67 Change password ...
Страница 68: ...InteliLite Global Guide 68 Note Use Up and Down button to select required level of password ...
Страница 69: ...InteliLite Global Guide 69 Log out from controller ...
Страница 70: ...InteliLite Global Guide 70 Note Enter invalid password to log out from controller 5 3 5 Information screen ...
Страница 71: ...InteliLite Global Guide 71 5 3 6 Language selection ...
Страница 72: ...InteliLite Global Guide 72 ...
Страница 78: ...InteliLite Global Guide 78 Image 5 13 Flowchart of start of diesel engine ...
Страница 80: ...InteliLite Global Guide 80 Image 5 14 Flowchart of start of gas engine ...
Страница 102: ...InteliLite Global Guide 102 5 4 15 Flowchart Image 5 30 Basic flowchart of controller sequences ...
Страница 170: ...InteliLite Global Guide 170 Image 8 5 Idle Time 1 Image 8 6 Idle Time 2 6 back to List of setpoints ...
Страница 550: ...InteliLite Global Guide 550 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...
Страница 582: ...InteliLite Global Guide 582 more information see Alarm types Level 2 on page 84 ...
Страница 617: ...InteliLite Global Guide 617 Image 9 29 I LB Image 9 30 I LB dimensions Note All dimensions are in mm ...