InteliLite Global Guide
99
Alarm states
An alarm can have following states:
Active alarm: the alarm condition persists, alarm delay has elapsed.
Inactive alarm: the alarm condition has disappeared, but the alarm has not been confirmed.
Confirmed alarm: the alarm condition persists, but the alarm has already been confirmed.
Image 5.16 Alarm List
Alarm types - Level 1
The level 1 alarm indicates that a value or parameter is out of normal limits, but has still not reached critical
level. This alarm does not cause any actions regarding the gen-set control.
Warning (Wrn)
The alarm appears in the Alarmlist and is recorded into the history log. Activates the output
as well as the standard alarm outputs (
and
).
Alarm indication only
The alarm indication only alarm does not perform any actions regarding gen-set control. Alarm is only displayed
in alarmlist.
History record only (HistRecOnl)
The event is recorded into the history. Standard alarm outputs (
and
) are
not activated.
Alarm types - Level 2
The level 2 level alarm indicates that a critical level of the respective value or parameter has been reached.
Note:
It is not possible to start the engine if any red level protection is active or not confirmed.
IMPORTANT: The gen-set can start by itself after acknowledging the alarms if there is no longer an
active red alarm and the controller is in AUTO or TEST mode!
Shutdown (Sd)
The alarm appears in the alarmlist and is recorded into the history log. It causes immediate stop of the Gen-set
without cooling phase. Also GCB breaker is open. The gen-set cannot be started again while there is a
Содержание InteliLite AMF25
Страница 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Страница 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Страница 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Страница 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Страница 199: ...InteliLite Global Guide 199 nominal speed Image 8 3 Idle Time 1 Image 8 4 Idle Time 2 6 back to List of setpoints ...
Страница 638: ...InteliLite Global Guide 638 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...
Страница 708: ...InteliLite Global Guide 708 Image 9 30 Inteli AIN8 Image 9 31 Inteli AIN8 dimensions Note All dimensions are in mm ...
Страница 714: ...InteliLite Global Guide 714 Image 9 32 Inteli IO8 8 Image 9 33 Inteli IO8 8 dimensions Note All dimensions are in mm ...
Страница 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Страница 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Страница 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...