InteliLite Global Guide
222
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
Disabled / 1–240 [min]
Default value
Disabled
Alternative config
NO
Step
1 min
Comm object
15766
Related applications
MRS
Config level
Advanced
Setpoint visibility
Always
Description
This setpoint enables battery charging and defines the time gen-set is running for to recharge battery. If
battery charging is enabled and battery undervoltage is detected for more than 5 minutes, gen-set is started
and will run for time defined in setpoint
Low Battery Charging Cycle
.
Battery charging is only initiated in AUT mode when no Shutdown alarm and Fuel Level alarm is active.
If there is battery undervoltage detected again after previous Charging Cycle is finished (and undervoltage
lasts more than 5 minutes) next Charging Cycle is initiated.
If controller is switched to MAN mode during battery charging, gen-set stay running regardless timer (
Low
Battery Charging Cycle
setpoint) elapsing. Gen-set is stopped by STOP button or by any SD alarm event
only in this case.
If there is
Charging Alternator Fail
alarm occurred during battery recharging period, current battery recharging
continues until time is elapsed. Next gen-set start due to battery undervoltage is blocked until controller is
restarted.
IMPORTANT: If controller is in MAN mode and the battery voltage is under the limit more
than 5 minutes engine is started immediately when controller is switched to AUT mode.
Note:
Low Battery Charging function is available only when separate MRS archive is used.
Low Battery Charging Cycle
Subgroup: Pulse Counters
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
0 ... 1 000 [-]
Default value
1
Alternative config
NO
Step
1
Comm object
10994
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Only if LBI
is configured
Description
This setpoint adjusts the rate of increasing of the Pulse Counter 1 function. The module counts pulses at the
input
and if the input pulses counter reaches value given by this setpoint, the
counter value
is increased by 1 and input pulses counter is reset to 0. Both
counter value and input pulses counter are stored in the nonvolatile memory.
Conversion Coefficient Pulse 1
Содержание InteliLite AMF25
Страница 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Страница 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Страница 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Страница 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Страница 199: ...InteliLite Global Guide 199 nominal speed Image 8 3 Idle Time 1 Image 8 4 Idle Time 2 6 back to List of setpoints ...
Страница 638: ...InteliLite Global Guide 638 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...
Страница 708: ...InteliLite Global Guide 708 Image 9 30 Inteli AIN8 Image 9 31 Inteli AIN8 dimensions Note All dimensions are in mm ...
Страница 714: ...InteliLite Global Guide 714 Image 9 32 Inteli IO8 8 Image 9 33 Inteli IO8 8 dimensions Note All dimensions are in mm ...
Страница 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Страница 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Страница 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...