InteliLite 9 Global Guide
327
Related FW
1.1.0
Related applications
AMF, MRS
Comm object
1253
Description
Output closes when the value of Fuel Level lies under the value of
setpoint and
opens when value of
is reached.
This output also can be closed by binary input
. In this case the binary
output
is closed until the binary input
is active
or until the value of
is reached.
Note:
Setpoints
and
are invisible until configuration of
this LBO.
Fuel Pump
back to Logical binary outputs alphabetically
LBO: G
Related FW
1.1.0
Related applications
AMF, MRS
Comm object
41
Description
The output controls the generator circuit breaker. Its state represents the breaker position requested by the
controller. The breaker must react within 5 seconds to a close or open command, otherwise an alarm is
issued.
Note:
InteliLite 9 controllers can work even without breaker feedbacks, in this case do not configure the
feedback to binary inputs.
Image 8.27 GCB Close command
GCB Close/Open
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...