InteliLite 9 Global Guide
250
Setpoint group
Basic settings
Related FW
1.1.0
Range [units]
1 .. 10 000 [A]
Default value
350 A
Alternative config
YES
Step
1 A
Comm object
12051
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
It is current limit for generator current protections and means maximal continuous generator current. Nominal
Current can be different from generator rated current value.
Note:
This value is used when binary input
is active.
Nominal Current 3
Setpoint group
Basic settings
Related FW
1.1.0
Range [units]
Monophase / Splitphase / 3Ph3Wire / High Leg D / 3Ph4Wire / Autodetect [-]
Default value
3Ph4Wire
Alternative config
YES
Step
[-]
Comm object
12060
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Mono Phase
Single phase voltage measurement L1-N
1x CT (Current Transformer)
Split Phase
Double Delta connection
Split Phase
Two phase voltage measurement L1,L2 with 180° phase shift
2x CT (Current Transformer)
3Ph3Wire
Ungrounded Delta connection
Open Delta
Ungrounded Wye
Corner-Grounded Delta
Split Phase Delta
Three phase voltage measurement L1,L2,L3 with 120° phase shift
No neutral is available 3x CT (Current Transformer)
High Leg D
High Leg Delta connection
Three phase voltage measurement L1,L2,L3
3x CT (Current Transformer)
Generator winding connection system
Connection type 3
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...