InteliLite4 AMF20 Global Guide
483
Image 8.39 GCB UV Coil close command
Image 8.40 GCB UV Coil open command
back to Logical binary outputs alphabetically
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
60
Description
The output is closed at the beginning of the Prestart Time period and opens when the Gen-set is fully
stopped.
If the Gen-set fails to start, then this output is opened after last cranking attempt.
The output also closes if the engine begins to rotate spontaneously.