InteliLite4 AMF20 Global Guide
384
Nominal Current 3
Setpoint group
Alternate Config
Related FW
1.3.0
Range [units]
1 .. 10 000 [A]
Default value
350 A
Alternative config
YES
Step
1 A
Comm object
12051
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
It is current limit for generator current protections and means maximal continuous generator current.
Nominal Current can be different from generator rated current value.
Note:
This value is used when binary input
is active.
Connection type 3
Setpoint group
Alternate Config
Related FW
1.3.0
Range [units]
Mono Phase / SplPhL1L2 / SplPhL1L3 / 3Ph3Wire / 3Ph4Wire / High Leg D /
Autodetect [-]
Default value
3Ph4Wire
Alternative config
YES
Step
[-]
Comm object
12060
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Connection type:
Mono Phase
Single phase voltage measurement L1-N
1x CT (Current Transformer)
SplPhL1L2
Double Delta connection
Split Phase
Two phase voltage measurement L1,L2 with 180° phase shift
2x CT (Current Transformer)
SplPhL1L3
Double Delta connection
Split Phase
Two phase voltage measurement L1,L3 with 180° phase shift
2x CT (Current Transformer)
3Ph3Wire
Ungrounded Delta connection
Open Delta
Ungrounded Wye
Содержание InteliLite 4 AMF 20
Страница 70: ...InteliLite4 AMF20 Global Guide 70 Image 5 13 WinScope 1000 screen select AirGate ...
Страница 107: ...InteliLite4 AMF20 Global Guide 107 Image 5 16 Flowchart of start of gas engine ...
Страница 602: ...InteliLite4 AMF20 Global Guide 602 Image 8 89 IGS PTM Image 8 90 IGS PTM dimensions ...
Страница 608: ...InteliLite4 AMF20 Global Guide 608 Image 8 91 Inteli AIN8TC Image 8 92 Inteli AIN8TC dimensions ...
Страница 612: ...InteliLite4 AMF20 Global Guide 612 Image 8 93 Inteli AIO9 1 Image 8 94 Inteli AIO9 1 dimensions ...