InteliLite4 AMF20 Global Guide
230
Choke Time
Setpoint group
Engine settings
Related FW
1.3.0
Range [units]
0 .. 3600 [s]
Default value
0 s
Alternative config
NO
Step
1 s
Comm object
13011
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Only when LBO
is configured and setpoint
= Fixed Time.
Description
Defines time logical binary output
is activated for when fixed time is used. When
setpoint
is set to
Temp Based
value,
Choke Time
value have no effect.
Note:
If setpoint
is set to nonzero value, total time the C
HOKE
output is
activated still matches value set by Choke Time setpoint. This mean Choke Timeshould be longer than
Choke Leadto ensure expected Choke behavior.