Nominal Voltage MonoPhase
Setpoint group
Basic settings
Related FW
1.3.0
Range [units]
80 .. 20 000 [V]
Default value
120 V
Alternative config
YES
Step
1 V
Comm object
20815
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Visible if one of the three
Setpoints is set to
Autodetect.
Description
This setting is used as phase-neutral
Nominal Voltage Ph-N (page 211)
by the voltage autodetect
function, if detected
is MonoPhase.
Gen VT Ratio
Setpoint group
Basic settings
Related FW
1.3.0
Range [units]
0.1 .. 500.0 [V/V]
Default value
1.0 V/V
Alternative config
NO
Step
0.1 V/V
Comm object
9579
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
Generator voltage potential transformers ratio. If no VTs are used, adjust this setpoint to 1.
Mains VT Ratio
Setpoint group
Basic settings
Related FW
1.3.0
Range [units]
0.1 .. 500.0 [V/V]
Default value
1.0 V/V
Alternative config
NO
Step
0.1 V/V
Comm object
9580
Related applications
AMF
Config level
Advanced
Setpoint visibility
Conditioned by the setpoint
Default Application Select (page 217)
Description
Mains voltage potential transformers ratio. If no VTs are used, adjust the setpoint to 1.
Содержание InteliLite 4 AMF 20
Страница 70: ...InteliLite4 AMF20 Global Guide 70 Image 5 13 WinScope 1000 screen select AirGate ...
Страница 107: ...InteliLite4 AMF20 Global Guide 107 Image 5 16 Flowchart of start of gas engine ...
Страница 602: ...InteliLite4 AMF20 Global Guide 602 Image 8 89 IGS PTM Image 8 90 IGS PTM dimensions ...
Страница 608: ...InteliLite4 AMF20 Global Guide 608 Image 8 91 Inteli AIN8TC Image 8 92 Inteli AIN8TC dimensions ...
Страница 612: ...InteliLite4 AMF20 Global Guide 612 Image 8 93 Inteli AIO9 1 Image 8 94 Inteli AIO9 1 dimensions ...