InteliDrive Lite, SW version 1.9
ID-FLX-Lite-1.9r1 Reference Guide.pdf,
©ComAp – August 2015
110
LiteEdit
429496729,4 Continue from 0,0
Step:
0,01
Range:
0,01 - +655,34
Default:
1,00
7.9.4 Counter mode 1, Counter mode 2
Setting of Counter 1 and Counter 2 mode:
Always:
Corresponding counter counts pulses all time.
Running:
Corresponding counter counts pulses only when engine is running.
OFF:
Corresponding counter does not count pulses. Default settings.
H
INT
The Total 1 and Total 2 values are visible in LiteEdit
– Values – Statistics.
The Total 1 and Total 2 values disappear from controller screen when both Counter modes 1 and 2
are switched OFF otherwise there is new screen between existing Statistics and Alarm list.
7.10 AIO module
7.10.1 AnlInAIO1, AIO2, AIO3, AIO4 lev1
[ ]
The level for IL-NT-AIO plug-in card Analog input 1, 2, 3, 4 alarm detection.
Step:
1
Range:
-100 - +10000
Default:
0
7.10.2 AnlInAIO1, AIO2, AIO3, AIO4 lev2
[ ]
The level for IL-NT-AIO plug-in card Analog input 1, 2, 3, 4 alarm detection.
Step:
1
Range:
-100 - +10000
Default:
0
7.10.3 AnlInAIO1, AIO2, AIO3, AIO4 del
[s]
Delay for IL-NT-AIO plug-in card Analog input 1, 2, 3, 4 alarm.
Step:
1s
Range:
0 - 180s
Default:
5s
H
INT
Plug-in analog inputs protection alarms can be configured following way
Configuration
Protection