ID-FLX Lite Global Guide
79
Abbreviation
Historical value
AI9
ID-Lite analog input 9 value
AIM1
Plug-in analog input 1 value
AIM2
Plug-in analog input 2 value
AIM3
Plug-in analog input 3 value
AIM4
Plug-in analog input 4 value
BIN
binary inputs ID-Lite
BIM
binary inputs of plug-in
BOUT
binary inputs ID-Lite
BOM
Binary output of plug-in
FC
ECU alarm Failure Code
FMI
ECU alarm Failure Mode Identifier
Note:
The ECU values are not recorded to history.
6.3 Diagnostic messages read from ECU
Diagnostic messages are read and displayed in extra ECU Alarm list. For Standard J1939 SPN (Suspect
Parameter Number), FMI (Failure Mode Identifier) and OC (Occurrence Counter) are shown together with verbal
description if available.
One SPN (Suspect Parameter Number) / FMI (Failure Mode Identify) couple describes one fail information. If
FMI is equal to 0 or 1, WRN is displayed in the ECU Alarm list. For any other FMI values, FLS is displayed.
Detail SPM/FMI code specification see in:
SAE Truck and Bus Control and Communications Network Standards Manual, SAE HS-1939 Publication
Or refer to corresponding engine manufacturer’s ECU error codes list.
Содержание InteliDrive FLX LITE
Страница 19: ...ID FLX Lite Global Guide 19 4 3 Terminal diagram and dimension ...
Страница 21: ...ID FLX Lite Global Guide 21 Example Default analog output curves ...
Страница 22: ...ID FLX Lite Global Guide 22 Example Wiring for Dacon gauges and IL NT AOUT8 ...
Страница 43: ...ID FLX Lite Global Guide 43 When you finish with adjusting the values click OK and Write to controller ...
Страница 44: ...ID FLX Lite Global Guide 44 5 2 Binary inputs and outputs ...
Страница 57: ...ID FLX Lite Global Guide 57 5 14 Display screens and pages structure ...
Страница 83: ...ID FLX Lite Global Guide 83 7 Communication 6 back to Table of contents ...
Страница 92: ...ID FLX Lite Global Guide 92 10 Appendix 10 2 Extension modules 225 6 back to Table of contents ...