4.7 How to install
To ensure proper function:
Wiring for binary inputs and analog inputs must not be run with power cables.
Analog and binary inputs should use shielded cables, especially when length >3 m.
Note:
During the configuration of controller or setpoints changes is required a password to the controller. The
default password from ComAp is “0”.
4.7.1 Grounding
To ensure proper function:
Use cable min. 2.5 mm
2
.
Brass M4×10 screw with star washer securing ring type grounding terminal shall be used.
The negative “–“ terminal of the battery has to be properly grounded.
Switchboard and engine has to be grounded in common spot.
Use cable as short as possible to the grounding point.
4.7.2 Wiring
Tightening torque, allowable wire size and type, for the Field-Wiring Terminals
Based on terminal type
PA256 – Specified tightening torque 0.5 Nm (4.4 In-lb)
2EDGK – Specified tightening torque 0.4 Nm (3.5 In-lb)
For field type terminals
Use only diameter 2.0 - 0.5 mm (12-26 AWG) conductor, rated for 75 °C minimum.
For Generator Voltage terminals
Use only diameter 2.0 - 0.5 mm (12-26 AWG) conductor, rated for 90 °C minimum.
IMPORTANT: Use copper conductors only!
Содержание InteliDrive FLX LITE
Страница 19: ...ID FLX Lite Global Guide 19 4 3 Terminal diagram and dimension ...
Страница 21: ...ID FLX Lite Global Guide 21 Example Default analog output curves ...
Страница 22: ...ID FLX Lite Global Guide 22 Example Wiring for Dacon gauges and IL NT AOUT8 ...
Страница 43: ...ID FLX Lite Global Guide 43 When you finish with adjusting the values click OK and Write to controller ...
Страница 44: ...ID FLX Lite Global Guide 44 5 2 Binary inputs and outputs ...
Страница 57: ...ID FLX Lite Global Guide 57 5 14 Display screens and pages structure ...
Страница 83: ...ID FLX Lite Global Guide 83 7 Communication 6 back to Table of contents ...
Страница 92: ...ID FLX Lite Global Guide 92 10 Appendix 10 2 Extension modules 225 6 back to Table of contents ...