ID-FLX Lite Global Guide
159
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 180 [s]
Default value
10
-
Step
1
Comm object
9270
Related applications
Description
Delay for Wrn/Sd AIN9 alarm.
Note:
Analog input 9 is configurable with basic two levels protection and it is voltage type of input with
range 0-10 V.
AIN9 Del
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 65535 [h]
Default value
10000
YES
Step
1
Comm object
9648
Related applications
Description
Counting down when engine is running, from the moment of setting up the value of working hours in
LiteEdit/controller. This value is counting and changing in LiteEdit/controller as well. Service time alarm
appears if reaches zero, until non-zero value is set.
Note:
Set the NextServTime = 65535 h to disable count down. The setpoint stays constant, but
Statistics value (visible in LiteEdit) displays #### invalid value.
NextServTime
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0.0 .. 5.0 [RPM]
Default value
0.0
-
Step
0.1
GearBoxRatio
Содержание InteliDrive FLX LITE
Страница 19: ...ID FLX Lite Global Guide 19 4 3 Terminal diagram and dimension ...
Страница 21: ...ID FLX Lite Global Guide 21 Example Default analog output curves ...
Страница 22: ...ID FLX Lite Global Guide 22 Example Wiring for Dacon gauges and IL NT AOUT8 ...
Страница 43: ...ID FLX Lite Global Guide 43 When you finish with adjusting the values click OK and Write to controller ...
Страница 44: ...ID FLX Lite Global Guide 44 5 2 Binary inputs and outputs ...
Страница 57: ...ID FLX Lite Global Guide 57 5 14 Display screens and pages structure ...
Страница 83: ...ID FLX Lite Global Guide 83 7 Communication 6 back to Table of contents ...
Страница 92: ...ID FLX Lite Global Guide 92 10 Appendix 10 2 Extension modules 225 6 back to Table of contents ...