ID-FLX Lite Global Guide
137
Setpoint group
ATT settings
Related FW
2.5.0
Range [units]
0 .. 10000 [-]
Default value
10000
YES
Step
1
Comm object
11855
Related applications
Description
Load limit regulator PI output upper limit.
Value of this Setpoint should be given in value of quantity without decimal point.
Example:
When AIN is configured in such way that Load limit set on 5 V to maintain the value
8.54 bar, then the value inserted to this Setpoint is 854.
LoadUpLimit
Setpoint group
ATT settings
Related FW
2.5.0
Range [units]
0 .. 10000 [-]
Default value
0
YES
Step
1
Comm object
11856
Related applications
Description
Load limit regulator PI output low limit.
Value of this Setpoint should be given in value of quantity without decimal point.
Example:
When AIN is configured in such way that Load limit set on 5 V to maintain the value
8.54 bar, then the value inserted to this Setpoint is 854.
LoadDnLimit
Setpoint group
ATT settings
Related FW
2.5.0
Range [units]
-200.0 .. +200.0 [%]
Default value
0
YES
Step
0.1
Comm object
11857
Related applications
Description
This is setpoint is giving Load limit gain factor.
Load Gain
Содержание InteliDrive FLX LITE
Страница 19: ...ID FLX Lite Global Guide 19 4 3 Terminal diagram and dimension ...
Страница 21: ...ID FLX Lite Global Guide 21 Example Default analog output curves ...
Страница 22: ...ID FLX Lite Global Guide 22 Example Wiring for Dacon gauges and IL NT AOUT8 ...
Страница 43: ...ID FLX Lite Global Guide 43 When you finish with adjusting the values click OK and Write to controller ...
Страница 44: ...ID FLX Lite Global Guide 44 5 2 Binary inputs and outputs ...
Страница 57: ...ID FLX Lite Global Guide 57 5 14 Display screens and pages structure ...
Страница 83: ...ID FLX Lite Global Guide 83 7 Communication 6 back to Table of contents ...
Страница 92: ...ID FLX Lite Global Guide 92 10 Appendix 10 2 Extension modules 225 6 back to Table of contents ...