ID-FLX Lite Global Guide
134
Setpoint group
Load limit
Related FW
2.5.0
Range [units]
-10000 .. +10000 [-]
Default value
0
YES
Step
1
Comm object
11840
Related applications
Description
Limit to open the
Value of this Setpoint should be given in value of quantity without decimal point.
Example:
When AIN is configured in such way that Load limit set on 5 V to maintain the value
8.54 bar, then the value inserted to this Setpoint is 854.
Reg CMP Off
Setpoint group
Load limit
Related FW
2.5.0
Range [units]
Reg Bias, LBi SpdUp/Dwn, CU AI1-CU AI9, AIO: AI1 - 4 [-]
Default value
Reg Bias
YES
Step
-
Comm object
13068
Related applications
N/A
Description
The setpoint is used for selecting what regulation will be used in AUTO mode in case automatic regulation is
disabled by
Disable. The options are:
Reg Bias – speed request will be set according to
, this function was standard
functionality of R Reg disable LBI in previous FW versions.
/
– it is possible to regulate speed manually by
/
even in Auto mode.
CU AI1-CU AI9, AIO: AI1 - 4 – it is possible to regulate speed manually by analog inputs even in Auto
mode
Note:
See
AUT SpdReq
Содержание InteliDrive FLX LITE
Страница 19: ...ID FLX Lite Global Guide 19 4 3 Terminal diagram and dimension ...
Страница 21: ...ID FLX Lite Global Guide 21 Example Default analog output curves ...
Страница 22: ...ID FLX Lite Global Guide 22 Example Wiring for Dacon gauges and IL NT AOUT8 ...
Страница 43: ...ID FLX Lite Global Guide 43 When you finish with adjusting the values click OK and Write to controller ...
Страница 44: ...ID FLX Lite Global Guide 44 5 2 Binary inputs and outputs ...
Страница 57: ...ID FLX Lite Global Guide 57 5 14 Display screens and pages structure ...
Страница 83: ...ID FLX Lite Global Guide 83 7 Communication 6 back to Table of contents ...
Страница 92: ...ID FLX Lite Global Guide 92 10 Appendix 10 2 Extension modules 225 6 back to Table of contents ...