ID-FLX Lite Global Guide
120
Setpoint group
Engine parameters
Related FW
2.5.0
Range [units]
0 .. 240 [s]
Default value
60
-
Step
1
Comm object
9815
Related applications
Description
Under normal conditions the engine must certainly stop within this period. The period starts by issuing stop
command.
Note:
Stop of engine is detected when all following conditions are met: RPM <2, Oil pressure <
StartingPOil and D+ input isn’t active.
Stop fail is detected if there is difference between those conditions.
Note:
In case when stop time period is lower than "stop engine detected" + 10 s, stop time period is
extended to this value due to safety reason. (stop engine detected = RPM<2, OilP not detected, D+ not
active)
Stop time
Setpoint group
Engine parameters
Related FW
2.5.0
Range [units]
DIESEL, GAS [-]
Default value
-
Step
-
Comm object
9100
Related applications
Description
Setpoint setting determines behavior of the Binary output FUEL SOLENOID.
DIESEL
Output closes 1 sec before Binary output STARTER.
The output opens if Emergency stop comes or Cooled engine is stopped and in
pause between repeated starts.
GAS
In this mode of operation the output closes to open the gas valve and enable the
engine to start. The delay of Fuel solenoid output activation in relation to Starter
output is defined by FuelSol offset. The output closes only if RPM > 30 (i.e. the
starter motor is engaged).
The output opens if there is any reason to stop the engine or in pause between
repeated starts.
Note:
In the case of gas engine, the underspeed protection cannot be blocked by the Sprinkler function.
For gas engines, it is strongly recommended to use the pick-up sensor, as non-zero RPM detection is
required during the start procedure.
Fuel solenoid
Содержание InteliDrive FLX LITE
Страница 19: ...ID FLX Lite Global Guide 19 4 3 Terminal diagram and dimension ...
Страница 21: ...ID FLX Lite Global Guide 21 Example Default analog output curves ...
Страница 22: ...ID FLX Lite Global Guide 22 Example Wiring for Dacon gauges and IL NT AOUT8 ...
Страница 43: ...ID FLX Lite Global Guide 43 When you finish with adjusting the values click OK and Write to controller ...
Страница 44: ...ID FLX Lite Global Guide 44 5 2 Binary inputs and outputs ...
Страница 57: ...ID FLX Lite Global Guide 57 5 14 Display screens and pages structure ...
Страница 83: ...ID FLX Lite Global Guide 83 7 Communication 6 back to Table of contents ...
Страница 92: ...ID FLX Lite Global Guide 92 10 Appendix 10 2 Extension modules 225 6 back to Table of contents ...