InteliDrive DCU Industrial 3.4.0 Global Guide
323
Sensor IS-AIN8
None
I-CB analog
Value is received from I-CB
Pt100/°C
Use
button to create new sensor characteristic.
Pt1000/°C
Ni100/°C
Ni1000/°C
Thermocouple J/°C
Thermocouple K/°C
Thermocouple L/°C
Adjust Range = maximal measured value
4 to 20 mA passive
Adjust Range
4 to 20 mA active
Adjust Range
0 to 20 mA passive
Adjust Range
0 ± 20 mA active
Adjust Range
0-250 ohm
Adjust Range
0-2400 ohm
Adjust Range
0 – 2.4 V
±1 V
0 - 10 V
0 - 100mV
Pt100/°F
Pt1000/°F
Ni100/°F
Ni1000/°F
Thermocouple J/°F
Thermocouple K/°F
Thermocouple L/°F
Cold Junction Compensation (CJC)
Cold junction compensation is also called reference junction compensation. When measuring temperature using
thermocouples, the reference terminal may not be held at 0°C, but at the surrounding temperature of T1°C
instead. Without any compensation, the thermocouple output will be changed (reduced) by T1°C. This is
compensated by adding potential difference to the IS-AIN8 corresponding to T1°C.
Содержание InteliDrive DCU Industrial
Страница 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Страница 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Страница 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Страница 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Страница 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...
Страница 281: ...InteliDrive DCU Industrial 3 4 0 Global Guide 281 6 back to Appendix 6 back to Table of contents...
Страница 294: ...InteliDrive DCU Industrial 3 4 0 Global Guide 294 Dimensions Note Unit is 35 mm DIN rail mounted Terminals...
Страница 306: ...InteliDrive DCU Industrial 3 4 0 Global Guide 306 Dimensions Note Unit is 35 mm DIN rail mounted...
Страница 314: ...InteliDrive DCU Industrial 3 4 0 Global Guide 314 Dimensions Unit is 35 mm DIN rail mounted Terminals...
Страница 350: ...InteliDrive DCU Industrial 3 4 0 Global Guide 350 6 back to Theory of binary inputs and outputs...