InteliDrive DCU Industrial 3.4.0 Global Guide
122
Setpoint group
Engine params
Related FW
3.4.0
Range [units]
[DIESEL, GAS]
Default value
DIESEL
Force value Alternative
config
Step
[-]
Comm object
9100
Related applications
AS, SS
Description
Selection of
FUEL SOLENOID
output function.
DIESEL:
The output is still closed except the
timer if stop command is sent to an
engine.
GAS:
Ignition is activated (binary output Ignition is closed) when RPM is over the 30 RPM (fix value). Gas
valve (binary output Gas is closed) is opened 1 sec after Ignition output. Gas output opens after stop
command or in pause between repeated start.
If the gas engine is unsuccessful in starting the starter output will stay energized 25 % longer in order to vent
the remaining gas.
Example of FUEL SOLENOID output behavior during unsuccessful start.
Fuel Solenoid
Setpoint group
Engine params
Related FW
3.4.0
Range [units]
0.0 .. 100.0 [%/s]
Default value
5
Force value
Alternative config
Step
0.1
Comm object
9984
Related applications
AS, SS
Description
Speed ramp setting for
/
, not for Analog input request.
BI Speed Ramp
Содержание InteliDrive DCU Industrial
Страница 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Страница 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Страница 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Страница 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Страница 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...
Страница 281: ...InteliDrive DCU Industrial 3 4 0 Global Guide 281 6 back to Appendix 6 back to Table of contents...
Страница 294: ...InteliDrive DCU Industrial 3 4 0 Global Guide 294 Dimensions Note Unit is 35 mm DIN rail mounted Terminals...
Страница 306: ...InteliDrive DCU Industrial 3 4 0 Global Guide 306 Dimensions Note Unit is 35 mm DIN rail mounted...
Страница 314: ...InteliDrive DCU Industrial 3 4 0 Global Guide 314 Dimensions Unit is 35 mm DIN rail mounted Terminals...
Страница 350: ...InteliDrive DCU Industrial 3 4 0 Global Guide 350 6 back to Theory of binary inputs and outputs...