IGS-NT Communication Guide
132
9.2.5 Modbus communication
via IB-NT
Modbus communication needs to be enabled in settings via IB-NT config.
Modbus is available as Modbus TCP or Modbus RTU over RS485.
Note:
For more information regarding IB-NT please see documentation
9.3 Modbus Protocol Description
9.3.1 Modbus TCP
Direct connection:
ETH
Port 502
Bridge connection:
IB-NT
Transfer mode TCP/IP
Function codes
3 (Read Multiple Registers)
6 (Write Single Register)
10 (Command)
16 (Write Multiple Registers)
The response to an incoming message depends on the network performace and on the controller
configuration. Typical response time is 25 ms.
Connection timeout is set to 15 seconds. If no message comes within the timeout then controller close the
connection.
Note:
Data structure is the same as Modbus RTU. Modbus TCP adds 6 bytes header before data. CRC
calculation is not used in Modbus TCP.
Содержание Inteli Mains NT BaseBox
Страница 12: ...IGS NT Communication Guide 12 2 1 IG IS IM NTC BB Communications...
Страница 13: ...IGS NT Communication Guide 13 2 2 IG IS IM NTC BB Terminals...
Страница 14: ...IGS NT Communication Guide 14 2 3 IG IS IM NTC BB Peripheral modules...
Страница 15: ...IGS NT Communication Guide 15 2 4 IG IS IM NTC BB Jumpers settings...
Страница 16: ...IGS NT Communication Guide 16 2 5 IG IM NT BB Communication...
Страница 17: ...IGS NT Communication Guide 17 2 6 IG IM NT BB Terminal...
Страница 18: ...IGS NT Communication Guide 18 2 7 IG IM NT BB Peripheral modules...
Страница 19: ...IGS NT Communication Guide 19 2 8 IG IM NT BB Jumper settings...
Страница 20: ...IGS NT Communication Guide 20 2 9 IG NT Communications Terminals...
Страница 22: ...IGS NT Communication Guide 22 2 11 IM NT Communications Terminals...
Страница 23: ...IGS NT Communication Guide 23 2 12 IS NT BB Communications Terminals...
Страница 65: ...IGS NT Communication Guide 65...
Страница 114: ...IGS NT Communication Guide 114 Image 7 2 InternetBridge NT wired internet connection...