InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf,
©ComAp – June 2013
129
N
OTE
:
Use low speed for long distance connection only. Set all connected
controllers to the same speed.
12.2.3.13
Setpoint: CAN2emptDetect
Group
Comms settings
Range [units]
DISABLED, ENABLED [-]
Related FW
3.0
Force value
possible
YES
Description
Enables the detection of missing other controllers on the CAN2 bus. If the
setpoint is in ENABLED position and there aren't any other controllers
detected on the CAN2 bus (the complete bus, not only within the logical
group) the alarm
CAN2Empty
is issued.
12.2.3.14
Setpoint: SHxOcol detect
Group
Comms settings
Range [units]
DISABLED, ENABLED [-]
Related FW
3.0
Description
This setpoint is used to enable/disable evaluation of collisions of virtual
shared peripherial modules. A collision means that there is more than one
source (shared outputs module) active on the CAN2 bus.
N
OTE
:
In certain situations multiple sites with bus tie breakers may need to have
more shared outputs sources as the CAN bus line is in some points
interrupted according to bus tie breakers position. Normally a collision would
be indicated if there were more sources on the bus and this setpoint can be
used to disable the evaluation of collisions in this special case.
12.2.3.15
Setpoint: CANAddrSwitch1
Group
Comms settings
Range [units]
[-]
Related FW
3.0
Содержание IM-NT
Страница 86: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 86 APPENDIX...
Страница 326: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 326 17 User Notes...
Страница 327: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 327...
Страница 328: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 328...