InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf,
©ComAp – June 2013
113
automatically when this setpoint is changed.
N
OTE
:
The actual setpoint units and range depend on setting of the Power format in
GenConfig.
N
OTE
:
If different voltage on BusL and on BusR is required the following procedure
is required:
Both setpoints (
) must be adjusted to
the same values according to the value of actual BusL or BusR nominal
voltage. E.g. BusR nominal is 400 V but BusL nominal is 415 V.
In this case both setpoints need to be adjusted to 400 V and setpoints of
corresponding protections for BusL need to be set assymetrically.
For 415 V on BusL it is typical to open BTB when voltage reaches 440 V or
390 V. Since the setpoint is adjusted to 400 V corresponding protection
setpoints need to be adjusted to
= 106% and
% (hence the desired values are reached).
12.2.2.9
Setpoint: Nomin current
Group
Basic Settings
Range [units]
1 .. 10000 [A]
Related FW
3.0
Force value
possible
YES
Description
This setpoint is used for adjusting the maximal allowed current at the busL.
The nominal current is used as the basis (100%) for busL thermal-
overcurrent protection (
), and for short current protection
N
OTE
:
and
to obtain correct busL current readings.
C
AUTION
!
The maximum measurable input current to the controller current terminals is
11A.
W
ARNING
!
Do not discconnect the CT terminals from the controller while there is
nonzero current in the CT primary circuit!
Содержание IM-NT
Страница 86: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 86 APPENDIX...
Страница 326: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 326 17 User Notes...
Страница 327: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 327...
Страница 328: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 328...