IGS-NT Installation Guide
60
Resistance input 0-2400
Ω
For more info see the chapter
Speed Governor Output
Boot jumper (upper one, rest of the jumpers is for internal use only)
Left to right: Pull up Bias /
120Ω / Pull down Bias
AOUT setting
Voltage 0-10VDC
Current 0-20mA
7.6.2.
Terminals, Inputs and Outputs
Function
Terminals
Note
Generator voltage
L1,L2,L3, (N)
3x120 / 277 Ph-N or 207 / 480 Ph-Ph VAC
(neutral not needed), max 350 / 600VAC *,
CAT III
Mains/Bus voltage
L1,L2,L3, (N)
3x120 / 277 Ph-N or 207 / 480 Ph-Ph VAC
(neutral not needed), max 350 / 600VAC,
CAT III
Generator current
L1k,L1l, L2k,L2l,
L3k,L3l
0 ÷ 5 Amps, max 10 A all time, 150 A for 2
sec
0 ÷ 1 Amp, max 2 Amps all time
Neutral/Mains
current
LNk,LNl
0 ÷ 5 Amps, max 10 A all time, 150 A for 2
sec
0 ÷ 1 Amp, max 2 Amps all time
IG-AVRi interface
AVRI-OUT, AVRI-
COM
TTL (5V PWM) interface to IG-AVRi
Power supply
+ , -
8 ÷ 36 VDC
D+
D plus
Inputs and outputs
Binary inputs
BI1 ÷ BI6
BI7 ÷ BI16
Activation to minus power supply.
Binary outputs
BO1 ÷ BO6
BO7 ÷ BO16
Load is connected to plus or to minus power
supply. (defined in GenConfig).
Analog inputs
AI1 ÷ AI4
Ohms, mA, Volts sensors
Analog outputs
SG-OUT, SG-COM
AOUT+, AOUT-
COM
Speed governor output interface (
10V / 5V
PWM; 500
– 3000Hz)
Configurable analog output, mA, V.
RPM
RPM-IN, RPM-COM
Min 2 Vpk-pk (from 4 Hz to 4 kHz)
Communication interface
RS232 (1)
D SUB9 (male)
PC: InteliMonitor, GenConfig or