IGS-NT-BC, SW Version 1.2.0,
©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
38
Time and Date Intercontroller Sharing
Time and Date are used mainly for History records. These values are shared between controllers that are
connected to CAN. When the value is changed in one controller, it sends its new value to all other controllers
that are connected to the same CAN bus and they update their time and date values and setpoints
accordingly.
Summer Time Mode
Summer Time Mode function may be enabled and disabled by user. It is possible to set if the controller is
located in the northern or southern hemisphere as well.
SummerTimeMode implemented in ComAp controllers is based on CET summer time which means:
•
Clock goes forward 1 hour at 2:00 a.m. on the last Sunday in March
•
Clock goes backwards 1 hour at 3:00 a.m. on the last Sunday in Octorber
N
OTE
:
Please be aware that in other regions summer time adjustments may be done in different time.
User Buttons
There are several User Buttons available in the controller. It is possible to set them on Soft Buttons in
InteliVision 5 or 8.
Selects which button is this function mapped to
(0
–
first button, 1
–
second button and so on)
Choose UserButton index and
its function (ON/OFF etc.)
Choose which colour will be
available for this button
Select which condition triggers
which coulour
Adjust text for the button
when it is active or inactive
Available functions for soft buttons are listed in the following table.
ON
Pressing the button changes the state of log. Binary Output U
SER BUTTON
X to closed.
When the output is closed and the button is pressed state is not changed.
OFF
Pressing the button changes the state of log. Binary Output U
SER BUTTON
X to opened.
When the output is opened and the button is pressed state is not changed.
ON/OFF
Pressing the button changes the state of log. Binary Output U
SER BUTTON
X to opened or
closed depending on previous state (it is changed to the opposite state).
P
ULSE
ON
Pressing the button issues log. Binary Output U
SER BUTTON
X to close for one second.
N
OTE
:
Repeated pressing of button during the closed period (one second) causes issuing other
puls of length of one second to be generated from the moment of button pushing.
H
INT
It is possible to lock User Button with password (go to tab Commands in GenConfig). User Buttons 1-5, 6-8
and 9-16 can be locked separately. It is also possible to use User Buttons in SCADA diagrams.