IGS-NT-BC, SW Version 1.2.0,
©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
234
•
Stop
button is pressed on any of external local/remote terminals or
•
stop
command is received via communication line or
•
the input
Binary output: BCBButnEcho
Related FW
3.0
Description
This output provides 1s pulse when:
•
BCB
button is pressed on the controller front panel or
•
BCB
button is pressed on any of external local/remote terminals or
•
BCB close/open
command is received via communication line or
•
the input
BCBButton
is activated.
Binary output: BCB status
Related FW
3.0
Description
This output indicates the BCB position, how it is internally considered in the
controller. The position is based on
input and optionally also on the
•
If only the positive feedback input is used the output mirrors the feedback.
•
If both feedbacks are used and they match each other the output
indicates the BCB position according to the feedbacks.
•
If both feedbacks are used, however they do not match each other, the
output remains in previous position when they matched.
The output can be used for indication of the BCB position.
Binary output: MCB status
Related FW
3.0
Description
This output indicates the MCB position, how it is internally considered in the
controller. The position is based on
input and optionally also on the
•
If only the positive feedback input is used the output mirrors the feedback.
•
If both feedbacks are used and they match each other the output
indicates the MCB position according to the feedbacks.
•
If both feedbacks are used, however they do not match each other, the
output remains in previous position when they matched.