![ComAp ID-Lite Скачать руководство пользователя страница 76](http://html1.mh-extra.com/html/comap/id-lite/id-lite_global-manual_2638907076.webp)
ID-FLX Lite & Telecom Global Guide
76
Abbreviation
Historical value
AI9
ID-Lite analog input 9 value
AIM1
Plug-in analog input 1 value
AIM2
Plug-in analog input 2 value
AIM3
Plug-in analog input 3 value
AIM4
Plug-in analog input 4 value
BIN
binary inputs ID-Lite
BIM
binary inputs of plug-in
BOUT
binary inputs ID-Lite
BOM
Binary output of plug-in
FC
ECU alarm Failure Code
FMI
ECU alarm Failure Mode Identifier
Note:
The ECU values are not recorded to history.
6.3 Diagnostic messages read from ECU
Diagnostic messages are read and displayed in extra ECU Alarm list. For Standard J1939 SPN (Suspect
Parameter Number), FMI (Failure Mode Identifier) and OC (Occurrence Counter) are shown together with verbal
description if available.
One SPN (Suspect Parameter Number) / FMI (Failure Mode Identify) couple describes one fail information. If
FMI is equal to 0 or 1, WRN is displayed in the ECU Alarm list. For any other FMI values, FLS is displayed.
Detail SPM/FMI code specification see in:
SAE Truck and Bus Control and Communications Network Standards Manual, SAE HS-1939 Publication
Or refer to corresponding engine manufacturer’s ECU error codes list.
Содержание ID-Lite
Страница 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Страница 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Страница 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Страница 40: ...ID FLX Lite Telecom Global Guide 40 When you finish with adjusting the values click OK and Write to controller...
Страница 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Страница 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...