ID-FLX Lite & Telecom Global Guide
170
Setpoint group
Sensors Spec
Related FW
2.5.0
Range [units]
-1000 .. +1000 [-]
Default value
0
-
Step
1
Comm object
11917
Related applications
Description
Calibrate the constant to adjust the measured value of ID-Lite analog inputs. Physical dimension of
calibrating constant is corresponding to analog input.
Note:
Calibration constants have to be adjusted when measured value is near the alarm level.
Calibr AI4
Setpoint group
Sensors Spec
Related FW
2.5.0
Range [units]
-1000 .. +1000 [-]
Default value
0
-
Step
1
Comm object
11918
Related applications
Description
Calibrate the constant to adjust the measured value of ID-Lite analog inputs. Physical dimension of
calibrating constant is corresponding to analog input.
Note:
Calibration constants have to be adjusted when measured value is near the alarm level.
Calibr AI5
Setpoint group
Sensors Spec
Related FW
2.5.0
Range [units]
-1000 .. +1000 [-]
Default value
0
-
Step
1
Comm object
11599
Related applications
Description
Calibrate the constant to adjust the measured value of ID-Lite analog inputs. Physical dimension of
calibrating constant is corresponding to analog input.
Note:
Calibration constants have to be adjusted when measured value is near the alarm level.
Calibr AI6
Содержание ID-Lite
Страница 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Страница 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Страница 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Страница 40: ...ID FLX Lite Telecom Global Guide 40 When you finish with adjusting the values click OK and Write to controller...
Страница 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Страница 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...